Sustainability of Data Center Digital Twins with Reinforcement Learning

AAAI 2024 · Reinforcement learning › Visual and representation RL · approach: Curriculum and environment design · 7 citations (OpenAlex)

Read the paperCheck your idea against 108,967 papers

AI-extracted summary. Written by AI from the paper's full text. Numbers and claims can be wrong or missing context, so check the paper before you cite or build on it.

Introduces DCRL-Green, an open-source OpenAI Gym-based multi-agent RL environment and digital twin for co-designing and controlling data center components (HVAC, load shifting, battery storage) to reduce carbon footprint.

Problem

Data center energy use and carbon emissions are growing with ML demand, but existing RL environments optimize individual DC components (HVAC setpoints, load shifting, battery scheduling) in isolation rather than jointly.

Approach

A modular, configurable data center digital twin exposed as a multi-agent Gym environment (built on RLlib) that jointly controls flexible load shifting, HVAC setpoints, and battery storage, with ASHRAE G36 as the rule-based reference and single- and multi-agent RL baselines.

Key results

Measured effects reported in the paper

What was changedWhereMeasuredEffect
Use PPO instead of ASHRAE Guideline36 for HVAC setpoint controlData center HVAC control · Single-agent HVAC controlCarbon footprint: 14839.00 -> 13726.56Helped
Use A2C instead of ASHRAE Guideline36 for HVAC setpoint controlData center HVAC control · Single-agent HVAC controlCarbon footprint: 14839.00 -> 13878.30Helped
Use multiagent MADDPG instead of ASHRAE G36 controlData center control · ArizonaEnergy reduction (%): 13.4 ± 0.48Helped
Use multiagent MADDPG instead of ASHRAE G36 controlData center control · ArizonaCarbon footprint reduction (%): 13.38 ± 0.62Helped
Use multiagent MADDPG instead of ASHRAE G36 controlData center control · New YorkEnergy reduction (%): 13.01 ± 0.12Helped
Use multiagent MADDPG instead of ASHRAE G36 controlData center control · New YorkCarbon footprint reduction (%): 12.77 ± 0.11Helped
Use multiagent MADDPG instead of ASHRAE G36 controlData center control · WashingtonEnergy reduction (%): 13.27 ± 0.06Helped
Use multiagent MADDPG instead of ASHRAE G36 controlData center control · WashingtonCarbon footprint reduction (%): 13.51 ± 0.05Helped

Limitations

Experimental setup

Datasets: data center workload profiles weather data grid carbon intensity data

Benchmarks: DCRL-Green default setup

Metrics: energy footprint carbon footprint (tonnes CO2) percentage reduction vs ASHRAE G36

Baselines: PPO A2C ASHRAE G36 MADDPG

Builds on: OpenAI Gym RLlib MADDPG EnergyPlus